The SMD commitment software does not automatically recognize start-up and shutdown profiles. Instead, the software considers a generator available for dispatch at or above EcoMin from the first hour scheduled online to the last hour scheduled online. To ensure that generators are committed in accordance with the physical constraints inherent in their design, the generator owners must adjust the generator parameters to recognize start-up and shutdown profiles.
A resource can clear in the Day-Ahead Market economically in the first hour of operation at amounts up to the greater of the Manual Response Rate multiplied by 60 or the EcoMin. Initially, the first hour of operation in the Day-Ahead Market clearing is converted into a start-time and the last hour into a shut down time. These times do not include any start-up or shut down profiles. Upon the close of the Day-Ahead Market, the Lead Market Participant or Designated Entity must review schedules for their resources and submit any start-up or shutdown profiles to the Forecaster. The Forecaster will consider these values along with the cleared Day-Ahead Market schedules and commit additional resources as required to meet capacity needs. If a generator is committed as a result of the Resource Adequacy Assessment (RAA) process, the Forecaster will contact the Lead Market Participant or Designated Entity to advise them of the intended commitment and request them to submit start-up and shutdown profiles for that resource. These values will be incorporated in the RAA commitment to ensure the software can consider all of the generator outputs in the solution.
The definitions for specific generator parameters used for commitment purposes are as follows:
Notification Time -The minimum time required from the time an order is received from ISO to come online to the time when the generator synchronizes to the system. Three different Notification Times (Hot, Intermediate, and Cold) can be submitted to allow the Participant to reflect the difference in the length of time for each condition.
Start Up Time -The total time required from the time the generator synchronizes to the system to the time the generator is released for dispatch to the ISO. Three different Start-Up Times (Hot, Intermediate, and Cold) can be submitted to allow the Participant to reflect the difference in the length of time for each condition.
Start Up Profile -This hourly profile describes the MWH of output expected during each of the hours in the Start-Up Time. When a resource is committed in the Day-Ahead Market or during the Resource Adequacy Assessment (RAA), the generator owner is required to submit the MWH expected for each of the hours from the time the generator synchronizes to the system to the time the generator is scheduled to be released for dispatch to the ISO. The number of hourly MWH values submitted should match the hours described in the applicable Hot, Intermediate, or Cold Start Time. If Start Time is thirty minutes or less, no Start-Up Profile should be submitted.
Shut Down Profile -This hourly profile describes the MWH of output that normally occurs in each hour from the time a generator is released for shut down from EcoMin by the ISO to the time the generator de-synchronizes from the system. If the resource can de-synchronize from EcoMin in less than thirty minutes, no Shut Down Profile should be submitted.
Hot to Cold Time -The time from de-synchronization that cold condition apply.
Hot to Inter Time -The time from de-synchronization that intermediate conditions apply.
Minimum Run Time -The minimum number of hours of operation at or above EcoMin that the generator owner requires the ISO recognize when committing the resource. The Minimum Run Time applies from the point where the generator is scheduled to be released for dispatch to the ISO from EcoMin to the point where the ISO releases the generator for shut down from EcoMin. Generator Owners should exclude the Start Up Profile hours (Start Up Time) and Shut Down Profile hours from the Minimum Run Time to ensure the software recognizes the constraints described by all of the generator parameters on cycling the resource in the commitment process. Resources clearing in the Day-Ahead Market will have schedules for consecutive hours that are equal to or greater than the Minimum Run Time.
Minimum Down Time -The minimum number of hours that the generator owner requires between the time the generator is released for shutdown by the ISO and the time the generator is scheduled to be released for dispatch to the ISO. Generator Owners should include the Shut Down Profile hours and the Start Up Profile (Start Time) hours in the Minimum Down Time to ensure the software recognizes the constraints described by all of the generator parameters on cycling the resource in the commitment process. Resources clearing in the Day-Ahead Market will have schedules that do not violate the Minimum Down Time.
No Load Cost -The cost associated with generation resource that is an online, but not supplying energy to the system. A better way to describe No Load would be to think of it as the amount, in dollars per hour, that participants with an ownership share in a generating unit scheduled in the New England wholesale energy market must be paid. The No Load cost amount is an additional payment to the start-up fee and price offered to supply electric energy for each hour.

